This brochure is intended to cover major exposures and control measures available
to mitigate hazards of server room. A data processing center / server room is
described as an area where computers are located, and these computers require
considerations for special power, process cooling, environmental controls and
access control.These days servers are used not only by IT and IT enabled
companies, but also by many manufacturing and service companies like banks or
companies who have computerized production or operation systems. A server room
is usually permanently unmanned, except for some sporadic and short-term
assignments. Most of the time these server rooms are unoccupied in the building
behind the glass doors on shelves housing electronic equipments with numerous
data cables or wires criss-crossing.
Minimum Requirements for Server Rooms:
CONSTRUCTION
 |
The data center must be located in a fire resistive, noncombustible, or tilt-up
construction. |
| |
{Walls – RCC structure/ solid masonry with fire resistance of not less than two hours} and {Floor and Roof – RCC slabs / floor and roof assemblies
with fire resistance rating of not less than two hours} |
 |
The materials in the data center and storage rooms must be constructed of and
contain |
| |
materials (e.g. curtains, carpeting, furniture, or fixtures) with a flame
spread rating less than 25. |
CUT-OFFS
 |
All rooms containing hardware, software, data, and support operations, etc.
must be segregated |
| |
from surrounding occupancies by a minimum 1-½ hour fire
resistance rated cut-off. |
LOCATION
 |
The Server room must be located at grade level (permanent flooring) or above.
Basement locations |
| |
should be avoided as they are considered to be with
inadequate protection. |
 |
Access to all areas of data processing and support operations must be restricted. |
HOUSEKEEPING
 |
There should not be unusual sources of ignition, flammable liquids, flammable
gases, or |
| |
accumulations of papers etc inside server room. |
FIRE DETECTION
 |
A smoke detection system in the Server room is required and must be connected
to acceptable |
| |
detection devices that includes: |
| |
 |
In the room: smoke detection of the Ionization, photoelectric or projected
beam types. |
| |
 |
Below the (raised) floor: Smoke detection of the Ionization, photoelectric or
projected beam types |
| |
|
if being used as an air plenum, or where the floor is of
combustible construction. |
AUTOMATIC SUPPRESSION SYSTEMS
 |
All Centers must have fixed automatic fire suppression systems, which includes: |
| |
 |
A sprinkler system design installed of NFPA standards. Wet or pre-action
systems are |
| |
|
acceptable with pre-action preferred. A dry pipe system is
not acceptable. |
| |
 |
A clean agent fire suppression system as listed in NFPA 2001, in the EDP
room and below |
| |
|
the floor in rooms not exceeding 25,000 square feet. The manufacturer and sales representative should be consulted in determining
the most suitable agent. |
LIQUID DETECTION
 |
All centers must have a system of water detection and/or floor devices,
supervised locally. |
| |
Water Detection Devices: There are two detection systems
available: spot and strip type. |
 |
Proper Floor Design consists of sloped floors leading to drains. The floor should
be partitioned |
| |
off with gutters to guide water into the drains. |
BATTERY PANEL
 |
With a back-up battery power in place, be aware of hydrogen generation from
banks of wet cell |
| |
batteries. Provide hydrogen detection and room ventilation
where hydrogen is generated. |
 |
Use dry cell batteries as they do not present the same exposures as wet cell
batteries and so the |
| |
need to isolate these UPS supplies is not essential. |
BUSINESS CONTINUITY
The cost of damaged equipment might pale in comparison to the loss of business due
to server downtime following an accident. The server needs to be up and running
24X7 by organizations. By the partial or total loss of this equipment, an entire
operation of vital nature could be temporarily paralyzed.
 |
Data Back Up: Data back up is a must. Back-up copies must be segregated in a
protected |
| |
environment (fire resistive safe, vault, room or remote site). There
must be at least one current back-up copy. |
 |
Two sets of Back Up: The more prudent businessman will make two sets of
back-up and |
| |
alternately update the sets. This procedure reduces the risk of
damaging a back-up in an emergency and having no alternate source of
information. |
 |
Disaster Recovery Plan (DRP): There shall be plan of action documented with
training to IT team in |
| |
case of major fire in server room. It shall include name and
contact details of incident controllers, ready reckoner for immediate
procurement of software and hardware, if possible alternate facility. |
HDFC ERGO can assist you in handling the fire risk of your server rooms. Our Risk
Consulting Service can offer you a Server Room Risk Review™ where our engineers
can visit your server rooms. They will review your security systems and processes
and offer suggestions on managing the risk. Based on this review, you could get
further advice from our specialists for insuring these risks under our suite of policies
designed keeping our clients’ requirements in mind.
Disclaimer: This document is advisory in nature only and is intended as a resource to
assist, in conjunction with your professional insurance advisor, in maintaining a loss
prevention program. It is not to be used or relied upon as a substitute for professional
advice. No part of this publication shall be reproduced without specific permission of
HDFC ERGO General Insurance Company Ltd. No liability is accepted for any loss or
damage however caused which may be directly or indirectly suffered in connection
with the use of the information contained herein.
Risk Consulting Services at HDFC ERGO General Insurance Company Limited
 |
Risk Survey Report (RSR) |
 |
Lightning Risk Assessment Report (LRAR) |
 |
Post Loss/Accident Survey Report (PLSR) |
 |
NatCat Analysis Report (NCAR) |
 |
Loss Prevention Brochures |
For more information & contact details, please visit below link:
http://www.hdfcergo.com/Commercial/RiskConsultingServices.html
HDFC ERGO General Insurance Company Limited
6th Floor, Leela Business Park, Andheri-Kurla Road Andheri East, Mumbai 400 059.
Registered Office: Ramon House, H T Parekh Marg 169, Backbay Reclamation, Mumbai 400 020.
Toll-free No. 1800 2 700 700 Fax: 91-22-6638 3699
E-mail
care@hdfcergo.com Website www.hdfcergo.com
Disclaimer: Please read the Terms & conditions before concluding the sale.Insurance is the subject matter of the solicitation.
IRDA Reg No. 125. |